ZW7-40.5 1250A Outdoor Vacuum Circuit Breaker Power Station Type

Ask Latest Price
Brand Name :Baikong
Model Number :ZW7-40.5
Certification :IEC,GB
Place of Origin :Sichuan,China
MOQ :10 Pieces(MOQ)
Price :$5000-$10000/ Piece
Payment Terms :T/T,, L/C, Western Union
Supply Ability :50000 Pieces/per Week
Delivery Time :5...15Days OR To be negotiated
Packaging Details :wooden box/standard exporting carton
Product name :ZW7-40.5/1250A outdoor vacuum circuit breaker power station type
Arc extinguishing method :vacuum circuit breaker
Leakage protector type :3P
Rated current :630A
Color :customizable
Working pressure :to ground/relative 42/48
Rated frequency :50Hz
Mechanical life :20000 times
weight :800kg
Number of poles :1P 3P
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

ZW7-40.5/1250A outdoor vacuum circuit breaker power station type

product information

Product name: ZW7-40.5 outdoor vacuum circuit breaker

Category: high voltage components

Product introduction: ZN7-40.5 outdoor high-voltage true master circuit breaker is used in AC 50Hz, voltage 40.5kV three-phase power system, as a function of breaking and closing load current, overload current and short-circuit current.

Overview of ZW7-40.5 outdoor vacuum circuit breaker

The ZN7-40.5 outdoor high-voltage true master circuit breaker is used in a three-phase power system with an AC 50Hz and a voltage of 40.5kV. It is used for breaking and closing load currents, overload currents and short-circuit currents.

Main functions of ZW7-40.5 outdoor vacuum circuit breaker

a. Using vacuum arc extinguishing, strong breaking capacity, long electrical life, and mechanical life of 10,000 times;

b. Simple structure, rabbit maintenance, long period of non-overhaul

c. Good insulation performance, strong anti-fouling tree;

d. It can be equipped with spring or electromagnetic operating mechanism, with reliable mechanical performance and frequent operation; no fire and explosion hazards;

e. Built-in current transformer, the instructor's accuracy can reach 0.2 level, which can realize three mutual protection;

f. Condensation controller is included, which can keep the circuit breaker running reliably at a certain temperature and humidity.

Environmental conditions for use of ZW7-40.5 outdoor vacuum circuit breaker

a. Ambient air temperature: upper limit +40℃, lower limit -30℃;

b. Altitude: ≤2000m (if the altitude needs to be increased, the rated insulation level will be increased accordingly);

c. Wind pressure: no more than 700Pa (equivalent to a wind speed of 34m/s);

d. Amplitude: earthquake intensity 8 degrees;

e. Pollution level: Level III;

f. Daily temperature difference: no more than 25℃

The main technical parameters

Serial number project unit data
1 Rated voltage kV 40.5
2 Rated insulation level Power frequency withstand voltage Dry 95
Wet 80
Lightning impulse withstand voltage (peak value) 185
3 Rated current A 1250,1600,2000
4 Rated short-circuit breaking current KA 20,25,31.5
5 Rated operating sequence Split -0.3s combined -180s combined
6 Rated short-circuit current breaking times timcs 12
7 Rated short-circuit making current (peak value) KA 50,63,80
8 Rated peak withstand current
9 Rated short-time withstand current KA 20,25,31.5
10 Rated short-circuit continuous current S 4
11 Average opening speed m/s 1.5±0.2
12 Average closing speed 0.7±0.2
13 Bounce time of contact closing S ≤2
14 Three-phase combination (opening) gate synchronization time difference ≤2
15 Closing time ≤150
16 Opening time ≤60
17 Mechanical life timcs 10000
18 Rated operating voltage and rated voltage of auxiliary circuit V DC220,110,24
AC220,110,24
19 DC resistance of each phase loop (without transformer) μΩ ≤100
20 Allowable wear thickness of dynamic and static contacts mm 3
21 weight kg 800