Add to Cart
40.5kV Assembly Type Three Phase Current Integrated Distribution Cabinet
Product Name: 40.5kV Assembly Type Three Phase Current Integrated Distribution Cabinet
Category: high voltage complete equipment series
Normal service conditions
Main technical parameters of the vacuum circuit breaker
Name | Unit | Figure |
Rated voltage | kV | 40.5 |
Rated frequency | Hz | 50 |
Fixed working frequency withstand voltage | kV | 95/1min |
Lightning impact withstand voltage | kV | 185 |
Rated current | A | 1250 1600 2000 |
Rated short-time tolerance current | KA | 20 25 31.5 |
Rated short open off current | kA | 20 25 31.5 |
Rated peak tolerance current | kA | 50 63 80 |
Rated short-circuit duration | ms | 4 |
Interlock time | ms | 30≤t≤60 |
Between time | S | 50≤t≤100 |
Rated short-circuit open current times | Order | 20 |
Mechanical life | Order | 10000 |
Levels of protection | IP43 |
Three, structural characteristics
1. The cabinet structure adopts the assembly type, and the circuit breaker adopts the trolley floor type structure;
2. Equipped with a new composite insulated vacuum circuit breaker, with the characteristics of simple interchangeability;
3. The screw screw propulsion mechanism is equipped with the manual frame, which can easily move the trolley and prevent misoperation and damage to the propulsion structure; 4. All operations can be carried out in the closed cabinet door;
5. The interlock between the main switch, trolley and switch cabinet door adopts mandatory mechanical locking to meet the "five prevention" function; 6. Enough cable room space to connect multiple cables; 7. Fast grounding switch for grounding and circuit short circuit;
8. Housing protection level IP3X, the car compartment door open state, protection level IP2X;
9. The product meets GB3906-1991.DL404-1997 and I international IEC-298 standard.